TEST METHODS FOR
IN-LINE AND FIREBOX
FLAME ARRESTORS
CSA - Z343


Revision History

First Edition Published
January, 1994

Revision 12

- April, 1992

Revision 11

- April, 1992

Revision 10

- March, 1992

Revision 09

- November, 1991

Revision 08

- June, 1991

Revision 07

- March, 1991

Revision 06

- December 1990

Revision 05

- May, 1990

Revision 04

- February, 1990

Revision 03

- October, 1989

Revision 02

- September, 1989

Revision 01

- March, 1989

Revision 00

- December, 1998

Test Methods for In-Line and Firebox Flame Arrestors
CSA Z-343 Second Edition


1. SCOPE

1.1

This Standard describes test methods for use in assessing the performance of flame arrestors intended for use with Class I, Group C and D flammable gases and vapors as defined in CSA Standard C22.1 - Canadian Electrical Code in applications such as flare stacks, firebox air intakes, and vent lines. This Standard does not apply to the details of construction, specification, selection, application, maintenance, or any of the other factors which must be considered for a suitable flame arrestor installation.

Note 1: See Appendix A for general background information concerning flame arrestors and test procedures.
Note 2: A vertical line in the left column of this draft document indicates that a change has occurred in this clause, relative to the First Edition of this Standard.
Note 3: Italicized text indicates that there is a definition for that term in the Definitions section of this Standard. Since the defined terms "flame arrestor", "firebox", and ''in-line" are used extensively, they are not italicized.

1.2
Standard applies to flame arrestor installations where the ambient temperature to which the arrestor is exposed is in the range -45°C to 100°C, and where the maximum operating pressure for flame arrestment is 108.25 kPa (absolute), unless otherwise stated by the manufacturer (see clause 1.4). This standard covers the testing of complete flame arrestor units only, (consisting, as a minimum, of a flame arrestor housing and flame arrestor element), and does not apply to the testing of individual components thereof. Performance tests of a flame suppression system, which may form part of a flame arrestor assembly, are not within the scope of this standard. A flame warning system is mandatory for any in-line flame arrestor being tested to this standard.

Note 1: The above temperature range is intended to represent normal outdoor seasonal temperature and pressure extremes to which a flame arrestor may be exposed in normal use.
Note 2: A device tested to this Standard may be operated at higher pressures, but flame arresting capabilities at pressures above 108.25 kPa (absolute) within the scope of this Standard, unless performance claims in this regard are stated by the manufacturer (see clause 1.4). Internal operating pressures would normally be expected to be lower than 108.25 kPa (absolute) where a low flow or loss of flow condition exists - the condition of most concern.
Note 3: If a flame suppression system is included with an in-line flame arrestor to enhance the overall performance of the system, the intent of this standard is to assess the performance of the in-line flame arrestor element only. Accordingly, this may require that a flame suppression system which is supplied with an in-line flame arrestor be disabled for certain tests in this Standard.

1.3
This standard does not apply to the following:

a) flame arrestors intended for installations in, on, or associated with explosion proof electrical enclosures as defined in CSA Standard C22.2 No. 30;
Note: Requirements for flame arrestors installed on explosion proof enclosures are stated in CSA Standard C22.2 No. 30.
b) flame arrestors used for intake and exhaust system explosion protection of diesel engines;
c) flame arrestor systems using other than porous media flame arrestor elements. These may be employed at the user's discretion, but not within the scope of this Standard;
Note: The intent of this clause is to limit the scope of this standard to cover only flame arrestors that use porous media to provide flame-arresting capability.The tests in this standard are designed to asses porous media-type flame arrestors only; application of these tests to other flame arresting technologies that do not use porous media may not be appropriate.
d) flame arrestors for use in oxygen enriched atmospheres;

1.4
The test requirements of this standard are minimum performance requirements. Performance claims specified by the manufacturer, such as may be made concerning flame arrestor operating pressure, which exceed these minimum stated performance requirements shall be verified in accordance with the procedures of this Standard,

2. REFERENCE PUBLICATIONS
All references shall be considered to refer to the latest edition and revision thereto, unless otherwise specified. This Standard refers to the the following Standards and the year dates shown indicate the latest editions available at the time of printing:

CSA Standards
C22.1-1986
Canadian Electrical Code
Part 1;
C22.2 No. 30-M1986 Explosion-proof Enclosures for use in Class 1 Hazardous Locations
Other useful references include:
Underwriters' Laboratories Standards
UL 525
Flame arrestors for use on Vents of Storage Tanks for Petroleum Oil and Gasoline Published by Underwriters' Laboratories Inc.
MSC/Circ. 373/Rev.1 International Maritime Organization, Maritime Safety Committee Circular No. 373, Revision No, 1.
Federal Register
Vol. 55, No. 120
June 21, 1990
Appendix A to Pad 154
Guidelines for Detonation Flame arrestors
API RP12N Recommended Practice for Operation, Maintenance, and Testing of Firebox Flame arrestors

Back To Home Page